Meyer Power Requirements
Cabinet count formula: Maximum long term continuous power draw at or below 70% of circuit ampacity
| Model | 15A @ 115V | 20A @ 115V | 15A @ 208V | 20A @ 208V |
|---|---|---|---|---|
| LINA | 4 (2.3A/ea) | 6 (2.3A/ea) | 8 (1.28A/ea) | 10 (1.28A/ea) |
| Leopard | 3 (3.0A/ea) | 4 (3.0A/ea) | 6 (1.66A/ea) | 8 (1.66A/ea) |
| 900-LFC | 2 (4.9A/ea) | 3 (4.9A) | 4 (2.77A) | 5 (2.77A) |
| Ultra-X20 | 11 (0.9A/ea) | 15 (0.9A/ea) | 18 (0.56A/ea) | 25 (0.56A/ea) |
| Ultra-X40 | 5 (1.9A/ea) | 7 (1.9A/ea) | 9 (1.11A/ea) | 12 (1.11A/ea) |